How to judge the failure of the four-way valve of the combined air conditioning unit?

Views: 0     Author: Site Editor     Publish Time: 2024-02-29      Origin: Site

Inquire

How to judge the failure of the four-way valve of the combined air conditioning unit?

The method to determine the failure of the four-way valve of the combined air conditioning unit includes the following steps:

1. The unit starts and the controller starts timing;

2. Determine the operating mode of the unit: if it is cooling mode, go to step 3; if it is heating mode, go to step 5;

3. After the unit runs for 5 minutes, the inner disk temperature Tnp of the indoor heat exchanger is obtained through the inner disk temperature sensor;

4. If Tnp ≥ 45℃ and lasts for 10 minutes, it will be judged that the four-way valve has failed, the unit will shut down and a fault will be reported; otherwise, it will be judged that the four-way valve is normal and the unit will continue to run;

5. Determine whether the unit is in defrost operation. If so, go to step 6; if not, go to step 8;

6. After running for 4 minutes, obtain the external disk temperature Twp of the outdoor heat exchanger through the external disk temperature sensor, and obtain the outdoor ambient temperature Tw through the outdoor ambient temperature sensor;

7. If Twp-Tw≤5℃, it will be judged that the four-way valve is invalid, the unit will shut down and a fault will be reported; otherwise, it will be judged that the four-way valve is normal and the unit will continue to run;

8. Obtain the outdoor ambient temperature Tw through the outdoor ambient temperature sensor; if Tw>-10℃, go to step 9; otherwise, go to step 11;

9. After running for 5 minutes, obtain the external disk temperature Twp of the outdoor heat exchanger through the external disk temperature sensor, and obtain the outdoor ambient temperature Tw through the outdoor ambient temperature sensor;

10. If Tw-Twp ≤ 0℃ and lasts for 5 minutes, the four-way valve is judged to be invalid, the unit is shut down and a fault is reported; otherwise, the four-way valve is judged to be normal and the unit continues to operate;

11. After running for 5 minutes, perform the following tests: obtain the external disk temperature Twp of the outdoor heat exchanger through the external disk temperature sensor; obtain the outdoor ambient temperature Tw through the outdoor ambient temperature sensor; obtain the unit high pressure HP through the outdoor high-pressure pressure sensor;

12. If Tw-Twp ≤ 2.5℃ and HP < 8bar and lasts for 10 minutes, the four-way valve is judged to be invalid and the unit is shut down and a fault is reported; otherwise, the four-way valve is judged to be normal and the unit continues to operate.


Product inquiry

Jiangping New environment - Focus on global cooling and warming

 
JPAC is professional Rooftop Air Conditioning Units, Combined AC Unit Manufacturers and suppliers in China, specialized in providing Water Chiller, Multiclone Dust Collector, Baghouse Dust Collector ... To buy or wholesale Rooftop Air Conditioning Units, Combined AC Unit available customized.

Contact Us

Mobile: +86-19105206010
E-mail: logos@jsjpxhj.com
Whatsapp: +86-19105206010
Website: www.jsjpac.com
 
Copyright © 2025 Jiangsu Jiangping New Environmental Technology Co., Ltd. All Rights Reserved.